Шаблон:Short description Шаблон:Infobox unit A circular mil is a unit of area, equal to the area of a circle with a diameter of one mil (one thousandth of an inch or Шаблон:Convert). It corresponds to approximately Шаблон:Val. It is a unit intended for referring to the area of a wire with a circular cross section. As the definition of the unit contains [[pi|Шаблон:Pi]], it is easy to calculate area values in circular mils when the diameter in mils is known.

The area in circular mils, Шаблон:Mvar, of a circle with a diameter of Шаблон:Mvar mils, is given by the formula:

<math>\{A\}_\mathrm{cmil} = \{d\}_\mathrm{mil}^2</math>

In Canada and the United States, the Canadian Electrical Code (CEC) and the National Electrical Code (NEC), respectively, use the circular mil to define wire sizes larger than 0000 AWG. In many NEC publications and uses, large wires may be expressed in thousands of circular mils, which is abbreviated in two different ways: kcmil[1] or MCM.[2] For example, one common wire size used in the NEC has a conductor diameter of 0.5 inches, or 500 mils, and thus a cross-section of <math>500^2 = 250{,}000</math> circular mils, written as 250 kcmil or 250 MCM, which is the first size larger than 0000 AWG used within the NEC.

1000 circular mil equals approximately Шаблон:Val, so for many purposes, a ratio of 2 MCM ≈ 1 mm2 can be used with negligible (1.3%) error.

Equivalence to other units of area

As a unit of area, the circular mil can be converted to other units such as square inches or square millimetres.

1 circular mil is approximately equal to:

  • 0.7854 square mils (1 square mil is about 1.273 circular mils)
  • 7.854 × 10−7 square inches (1 square inch is about 1.273 million circular mils)
  • 5.067 × 10−10 square metres
  • 5.067 × 10−4 square millimetres
  • 506.7 μmШаблон:Sup

1000 circular mils = 1 MCM or 1 kcmil, and is (approximately) equal to:

Therefore, for practical purposes such as wire choice, 2 kcmil ≈ 1 mmШаблон:Sup is a reasonable rule of thumb for many applications.

Square mils

In square mils, the area of a circle with a diameter of 1 mil is:

<math display=block>A = \pi r^2 = \pi \left( \frac{d}{2} \right) ^2 = \frac{\pi d^2}{4} = \rm \frac{\pi \times (1~mil)^2}{4} = \frac{\pi}{4}~mil^2 \approx 0.7854~mil^2. </math>

By definition, this area is also equal to 1 circular mil, so:

<math display=block>\rm 1~cmil = \frac{\pi}{4}~mil^2.</math>

The formula for the area of an arbitrary circle in circular mils can be derived by applying this conversion factor to the standard formula for the area of a circle (which gives its result in square mils).

<math display=block> \begin{align} A &= \pi r^2 = \pi \left( \frac{d}{2} \right) ^2 = \frac{\pi d^2}{4} && (\text{Area in mil}^2)\\[2ex]

 &= \frac{\pi d^2}{4} \times \frac{4~\textrm{cmil}}{\pi~\textrm{mil}^2} && (\text{Convert to cmil})\\[2ex]
 &= d^2 ~ \mathrm{cmil/mil^2} && (\text{Result is in cmil}).

\end{align} </math>

Square inches

To equate circular mils with square inches rather than square mils, the definition of a mil in inches can be substituted:

<math>

\begin{align} \rm 1~cmil &= \rm \frac{\pi}{4}~mil^2 = \frac{\pi}{4}~(0.001~in)^2\\[2ex]

          &= \rm \frac{\pi}{4{,}000{,}000}~in^2 \approx 7.854 \times 10^{-7}~in^2

\end{align} </math>

Square millimetres

Likewise, since 1 inch is defined as exactly 25.4Шаблон:Nbspmm, 1Шаблон:Nbspmil is equal to exactly 0.0254Шаблон:Nbspmm, so a similar conversion is possible from circular mils to square millimetres:

<math>

\begin{align} \rm 1~cmil &= \rm \frac{\pi}{4}~mil^2 = \frac{\pi}{4}~(0.0254~mm)^2 = \frac{\pi \times 0.000\,645\,16}{4}~mm^2 \\[2ex]

          &= \rm 1.6129\pi \times 10^{-4}~mm^2 \approx 5.067 \times 10^{-4}~mm^2

\end{align} </math>

Example calculations

A 0000 AWG solid wire is defined to have a diameter of exactly Шаблон:Convert. The cross-sectional area of this wire is:

Formula 1: circular mil

Note: 1 inch = 1000 mils

<math>\begin{align}
 d &= \rm 0.46~inches = 460~mil \\
 A &= d^2 ~ \rm cmil/mil^2 = (460~mil)^2 ~ cmil/mil^2 = 211{,}600~cmil.

\end{align}</math>

(This is the same result as the AWG circular mil formula shown below for Шаблон:Math)

Formula 2: square mil

<math>\begin{align}
 d &= \rm 0.46~inches = 460~mils \\
 r &= {d \over 2} = \rm 230~mils \\
 A &= \pi r^2 = \rm \pi \times (230~mil)^2  = 52{,}900 \pi~mil^2 \approx 166{,}190.25~mil^2

\end{align}</math>

Formula 3: square inch

<math>\begin{align}
 d &= \rm 0.46~inches \\
 r &= {d \over 2} = \rm 0.23~inches \\
 A &= \pi r^2 = \rm \pi \times (0.23~in)^2  = 0.0529 \pi \approx 0.16619~in^2

\end{align}</math>

Calculating diameter from area

When large diameter wire sizes are specified in kcmil, such as the widely used 250 kcmil and 350 kcmil wires, the diameter of the wire can be calculated from the area without using Шаблон:Pi:

We first convert from kcmil to circular mil

<math>\begin{align}
 A &= \rm 250~kcmil = 250{,}000~\text{cmil} \\
 d &= \sqrt{A ~ \mathrm{mil^2/cmil}} \\
 d &= \rm \sqrt{(250{,}000~cmil) ~ mil^2/cmil} = 500~mil = 0.500~inches

\end{align}</math>

Thus, this wire would have a diameter of a half inch or 12.7 mm.

Metric equivalent

Some tables give conversions to circular millimetres (cmm).[3][4] The area in cmm is defined as the square of the wire diameter in mm. However, this unit is rarely used in practice. One of the few examples is in a patent for a bariatric weight loss device.[5]

<math> \rm 1~cmm = \left( \frac{1000}{25.4} \right) ^2~cmil \approx 1{,}550~cmil </math>

AWG circular mil formula

The formula to calculate the area in circular mil for any given AWG (American Wire Gauge) size is as follows. <math>A_n</math> represents the area of number <math>n</math> AWG.

<math>A_n = \left (5 \times 92^{(36 - n)/39}\right)^2</math>

For example, a number 12 gauge wire would use <math>n = 12</math>:

<math>\left(5 \times 92^{(36-12)/39}\right)^2 = 6530~\textrm{cmil}</math>

Sizes with multiple zeros are successively larger than 0Шаблон:NbspAWG and can be denoted using "number of zeros/0"; for example "4/0" for 0000Шаблон:NbspAWG. For an <math>m</math>/0Шаблон:NbspAWG wire, use

<math>n = -(m - 1) = 1 - m</math> in the above formula.

For example, 0000Шаблон:NbspAWG (4/0Шаблон:NbspAWG), would use <math>n = -3</math>; and the calculated result would be 211,600 circular mils.

Standard sizes

Standard sizes are from 250 to 400 in increments of 50Шаблон:Nbspkcmil, 400 to 1000 in increments of 100Шаблон:Nbspkcmil, and from 1000 to 2000 in increments of 250Шаблон:Nbspkcmil.[6]

The diameter in the table below is that of a solid rod with the given conductor area in circular mils. Stranded wire is larger in diameter to allow for gaps between the strands, depending on the number and size of strands.

Standard kcmil wire sizes
& solid copper equivalents
Area Diameter NEC copper wire
ampacity with
60/75/90 °C
insulation (A)[7]
(kcmil,
MCM)
(mm2) (in) (mm)
250 126.7 0.500 12.70 215 255 290
300 152.0 0.548 13.91 240 285 320
350 177.3 0.592 15.03 260 310 350
400 202.7 0.632 16.06 280 335 380
500 253.4 0.707 17.96 320 380 430
600 304.0 0.775 19.67 355 420 475
700 354.7 0.837 21.25 385 460 520
750 380.0 0.866 22.00 400 475 535
800 405.4 0.894 22.72 410 490 555
900 456.0 0.949 24.10 435 520 585
1000 506.7 1.000 25.40 455 545 615
1250 633.4 1.118 28.40 495 590 665
1500 760.1 1.225 31.11 520 625 705
1750 886.7 1.323 33.60 545 650 735
2000 1013.4 1.414 35.92 560 665 750

Note: For smaller wires, consult Шаблон:Slink.

See also

References

Шаблон:Reflist

  1. "Popular Acronyms" Шаблон:Webarchive. NEMA
  2. "Energy Acronyms", California Energy Commission
  3. Charles Hoare, The A.B.C. of Slide Rule Practice, p. 52, London: Aston & Mander, 1872 Шаблон:Oclc
  4. Edwin James Houston, A Dictionary of Electrical Words, Terms and Phrases, p. 135, New York: W. J. Johnston, 1889 Шаблон:Oclc
  5. Greg A. Lloyd, Bariatric Magnetic Apparatus and Method of Manufacturing Thereof, US patent Шаблон:Patent, 9 July 2013.
  6. NFPA 70-2011 National Electrical Code 2011 Edition Шаблон:Webarchive. Table 310.15(B)(17) page 70-155, Allowable Ampacities of Single-Insulated Conductors Rated Up to and Including 2000 Volts in Free Air, Based on Ambient Air Temperature of 30°C (86°F).
  7. NFPA 70 National Electrical Code 2008 Edition Шаблон:Webarchive. Table 310.16 page 70-148, Allowable ampacities of insulated conductors rated 0 through 2000 volts, 60°C through 90°C, not more than three current-carrying conductors in raceway, cable, or earth (directly buried) based on ambient temperature of 30°C. Extracts from NFPA 70 do not represent the full position of NFPA and the original complete Code must be consulted. In particular, the maximum permissible overcurrent protection devices may set a lower limit.