Category 5 cable (Cat 5) is a twisted pair cable for computer networks. Since 2001, the variant commonly in use is the Category 5e specification (Cat 5e). The cable standard provides performance of up to 100 MHz and is suitable for most varieties of Ethernet over twisted pair up to 2.5GBASE-T[1][2][3][4] but more commonly runs at Шаблон:Nowrap (Gigabit Ethernet) speeds. Cat 5 is also used to carry other signals such as telephone and video.

This cable is commonly connected using punch-down blocks and modular connectors. Most Category 5 cables are unshielded, relying on the balanced line twisted pair design and differential signaling for noise suppression.

Standards

Category 5 is currently defined in ISO/IEC 11801, IEC 61156 and EN 50173, though it was originally defined in ANSI/TIA/EIA-568-A (with clarification in TSB-95).[5] These documents specify performance characteristics and test requirements for frequencies up to 100 MHz.

The cable is available in both stranded and solid conductor forms. The stranded form is more flexible and withstands more bending without breaking. Patch cables are stranded. Permanent wiring used in structured cabling is solid. The category and type of cable can be identified by the printing on the jacket.[6]

The Category 5 specification requires conductors to be pure copper. There has seen a rise in counterfeit cables, especially of the copper-clad aluminum (CCA) variety.[7] This has exposed the manufacturers and installers of such fake cable to legal liabilities.[8]

Variants and comparisons

The Category 5e specification improves upon the Category 5 specification by further mitigating crosstalk.[9] The bandwidth (100 MHz) and physical construction are the same between the two,[10] and most Cat 5 cables actually happen to meet Cat 5e specifications even though they are not certified as such.[11] Category 5 was deprecated in 2001 and superseded by the Category 5e specification.[12]

The Category 6 specification improves upon the Category 5e specification by extending frequency response and further reducing crosstalk. The improved performance of Cat 6 provides 250 MHz bandwidth.[12] Category 6A cable provides 500 MHz bandwidth. Both variants are backward compatible with Category 5 and 5e cables.

Termination

Шаблон:T568A Wiring Шаблон:T568B Wiring

Файл:CAT-5E-Wall Outlet.jpg
A Cat 5e dual-port wall-mount assembly showing the two wiring schemes: A for T568A, B for T568B
Файл:Cat 5.jpg
Category 5 patch cable in T568B wiring

Cable types, connector types and cabling topologies are defined by ANSI/TIA-568. Category 5 cable is nearly always terminated with 8P8C modular connectors (often referred to incorrectly as RJ45 connectorsШаблон:Sfn[13][14]). The cable is terminated in either the T568A scheme or the T568B scheme. The two schemes work equally well and may be mixed in an installation so long as the same scheme is used on both ends of each cable.

Applications

Category 5 cable is used in structured cabling for computer networks such as Ethernet over twisted pair. The cable standard prescribes performance parameters for frequencies up to Шаблон:Nowrap and is suitable for Шаблон:Nowrap, Шаблон:Nowrap (Fast Ethernet), Шаблон:Nowrap (Gigabit Ethernet), and Шаблон:Nowrap. Шаблон:Nowrap and Шаблон:Nowrap Ethernet connections require two wire pairs. 1000BASE-T and faster Ethernet connections require four wire pairs. Through the use of power over Ethernet (PoE), power can be carried over the cable in addition to Ethernet data.

Cat 5 is also used to carry other signals such as telephony and video.[15] Шаблон:AnchorIn some cases, multiple signals can be carried on a single cable; Cat 5 can carry two conventional telephone lines as well as 100BASE-TX in a single cable.[16][17][18][19][20] The USOC/RJ-61 wiring standard may be used in multi-line telephone connections. Various schemes exist for transporting both analog and digital video over the cable. HDBaseT Шаблон:Nowrap is one such scheme.[21]

Characteristics

The use of balanced lines helps preserve a high signal-to-noise ratio despite interference from both external sources and crosstalk from other pairs.

Electrical characteristics for a commercially available Cat 5e UTP cable product
Property Nominal Tolerance Unit ref
Шаблон:Nowrap, Шаблон:Nowrap 100 ± 15 Шаблон:Nowrap Шаблон:Nowrap
Шаблон:Nowrap Шаблон:Nowrap 100 ± 5 Шаблон:Nowrap Шаблон:Nowrap
DC loop resistance ≤ 0.188 Шаблон:Nowrap Шаблон:Nowrap
Propagation speed relative to the speed of light 0.64 1 Шаблон:Nowrap
Propagation delay 5.30 Шаблон:Nowrap Шаблон:Nowrap
Delay skew Шаблон:Nowrap < 0.20 Шаблон:Nowrap Шаблон:Nowrap
Capacitance at Шаблон:Nowrap 52 Шаблон:Nowrap Шаблон:Nowrap
Max tensile load, during installation 100 Шаблон:Nowrap Шаблон:Nowrap
Wire diameter (24 AWG; Шаблон:Nowrap) Шаблон:Nowrap mm Шаблон:Nowrap
Operating temperature −55 to +60 Шаблон:Nowrap Шаблон:Nowrap
Шаблон:Nowrap
(Шаблон:Nowrap)[22]
125 Шаблон:Nowrap Шаблон:Nowrap

Insulation

Outer insulation is typically polyvinyl chloride (PVC)[23] or low smoke zero halogen (LS0H).Шаблон:Citation needed

Example materials used as insulation in the cable[24]
Acronym Material
PE Polyethylene
FP Foamed polyethylene
FEP Fluorinated ethylene propylene
FFEP Foamed fluorinated ethylene propylene
AD/PE Air dielectric/polyethylene
LSZH or LS0H Low smoke, zero halogen
LSFZH or LSF0H Low smoke and fume, zero halogen

Bending radius

Most Category 5 cables can be bent at any radius exceeding approximately four times the outside diameter of the cable.[25][26]

Maximum cable segment length

The maximum length for a cable segment is Шаблон:Convert per TIA/EIA 568-5-A.[27] If longer runs are required, the use of active hardware such as a repeater or switch is necessary.[28][29] The specifications for 10BASE-T networking specify a 100-meter length between active devices.[30] This allows for 90 meters of solid-core permanent wiring, two connectors and two stranded patch cables of 5 meters, one at each end.[31]

Conductors

Since 1995, solid-conductor UTP cables for backbone cabling is required to be no thicker than 22 American Wire Gauge (AWG) and no thinner than 24 AWG, or 26 AWG for shorter-distance cabling. This standard has been retained with the 2009 revision of ANSI TIA/EIA 568.[32]

Although cable assemblies containing four pairs are common, Category 5 is not limited to four pairs. Backbone applications involve using up to Шаблон:Nowrap.[33]

Individual twist lengths

The distance per twist is commonly referred to as pitch. Each of the four pairs in a Cat 5 cable has differing pitch to minimize crosstalk between the pairs. The pitch of the twisted pairs is not specified in the standard.

Environmental ratings

Шаблон:Split

United States and Canada fire certifications[34]
Class Phrase Description Standards
LSZH Communications low-smoke zero halogen NES‑711, NES‑713, MIL‑C‑24643, UL 1685
CMP Communications plenum Insulated with fluorinated ethylene propylene (FEP) and polyethylene (PE) and jacketed with low-smoke polyvinyl chloride (PVC), due to better flame test ratings. CSA FT6[35] or NFPA 262 (UL 910)
CMR Communications riser Insulated with high-density polyolefin and jacketed with low-smoke polyvinyl chloride (PVC).

UL 1666

CMG Communications general purpose CSA FT4
CM Communications Insulated with high-density polyolefin, but not jacketed with PVC and therefore is the lowest of the three in flame resistance. UL 1685 (UL 1581, Sec. 1160) Vertical-Tray
CMX Communications residential UL 1581, Sec. 1080 Шаблон:No wrap
CMH CSA FT1

Some cables are "UV-rated" or "UV-stable" meaning they can be exposed to outdoor UV radiation without significant degradation.[36]

Plenum-rated cables are slower to burn and produce less smoke than cables using a mantle of materials like PVC. Plenum-rated cables may be installed in plenum spaces where PVC is not allowed.[37]Шаблон:Self-published inline

Shielded cables (FTP or STP) are useful for environments where proximity to RF equipment may introduce electromagnetic interference, and can also be used where eavesdropping likelihood should be minimized.